Hanyoung Programmable Temperature Controller Model TH300
ข้อมูลสินค้า
-
รหัสสินค้า
TH1
-
แก้ไขล่าสุดเมื่อ
01/12/2016 13:02
ดาวน์โหลดไฟล์ PDF
-
รายละเอียดสินค้า
- TH300
- - Touch panel color LCD screen
- Precise control
- 100 patterns (Total 2,000 segments, 100 SEG / PTN)
- Temperature / humidity independent PID control
- Various alarm functions
- Digital input (DI) 4 contacts, digital output (DO) 12 contacts
- Communication function (RS232 or RS485, selected by the suffix code)
Suffix code
Model Code Information TH300 Programmable Temperature&Humidity controller (DIN 96 × 96) Communication 1 RS232C communication 2 RS485 / 422 communication Language (optional) 1 Korean and English (Standard type) 2 English and Chinese (Simplified Chinese Characters) 3 English and Chinese (Traditional Chinese Characters) Specification
[Input] Temperature sensor
(Dry)RTP (Pt100 Ω) or 0 - 5 V DC
※ 4 - 20 ㎃ DC (external resistance 250Ω)
※ Pt100 Ω (IEC 751)Humidity sensor
(Wet)Sampling time 500 ms Measurement range Temperature : -100.0 ~ 500.0 ℃ Humidity : 0.0 ~ 100.0 % RH Digital Input (DI) 4 contacts (1a X 4)
[Function] Display accuracy Temperature : ±0.2 % of FS
Humidity : ±2 % of FSInsulation resistance 500 V DC min 10 ㏁ (between the primary and secondary terminal,
between the primary / secondary terminal and earth terminal)Dielectric strength 2500 V AC 50 / 60 ㎐ (between the primary and secondary terminal)
[Operation environment] Ambient temperature 0 ~ 50 ℃ Ambient humidity 20 ~ 90 % RH (without dew condensation) Storage temperature -25 ~ 70 ℃ Vibration resistance 10 - 55 ㎐, amplitude 0.75 mm, 3 directions 4 times, 5 min/cycle. Shock resistance 147 ㎨, 3 directions 3 times. Dimension 96(W) X 96(H) X 100(D) Weight approx. 582 kg (body + fastener)
[Standard specification] Power supply voltage 100 -240 V AC, voltage fluctuation : ±10 % Power frequency 50 - 60 ㎐ Power consumption 10 VA max Ambient temperature 0 ~ 50 ℃ Ambient humidity 20 ~ 90 % RH (No dew condensation allowed) Storage temperature -25 ~ 70 ℃ Vibration resistance 10 - 55 ㎐, amplitude 0.75 mm, 3 directions for 4 times, 5 min/cycle Shock resistance 147 ㎨, to 3 directions for 3 times Dimension 96(W) X 96(H) Weight Approx. 850 g (included the weight of box)
[Monitor specification] Screen rating TFT LCD (70.08 X 52.56 mm : 3.5") Number of Pixels 320 X RGB X 240 Back light Edge Light LED B/L Back light life expectancy Approximately 40,000 hours Touch type Register type (4 wires) Language Korean/English, Korean/Chinese (Simplified Chinese Characters,
English/Chinese (Traditional Chinese Characters). *selected by the suffix code
[Communication] Applicable rating EIA - RS232C, RS485/422 Max number of connection RS232C 1 : 1 RS485/422 32 devices max (includes the master). ※ address 1 ~ 999 Communication type RS232C Full Duplex RS485/422 2 wires type half duplex Synchronous type RS232, 485/422 Asynchronous mode RS232C Approx. within 10 m RS485/422 Approx. within 1.2 km RS232C, 485/422 9600 / 19200 / 38400 bps Data Length RS232C, 485/422 7/8 Bits Parity Bit RS232C, 485/422 NONE / EVEN / ODD Stop Bit RS232C, 485/422 1 / 2 Bit (s) Protocol RS232C, 485/422 PCLINK / PCLINK + CRC / MODBUS - RTU Response Time RS232C, 485/422 0 - 999 ms
[Output] Control output (OUT) SSR ON : 24 V DC pulse voltage, OFF : below 0.1 V DC
Pulse voltage(resistive load above 800Ω)Cycle time : 1 ~ 1000 sec Retransmission output (RET) Temperature 4 - 20 ㎃ DC (resistive load 600 Ω max)
present value (PV), output amount (MV), set value(SV)
※ by the internal selectionHumidity Resolving power 7000 max (regarding 4 - 20 ㎃) Renewal time 500 ms Digital output (DO) Relay 8 contacts (1a X 8 contacts)
N.O : 30 V DC 5 A, 240 V AC 5 ATransistor 4 contacts (Open collector output).
24 V DC 300 ㎃ max
[Function] Input Input compensation Temperature : -100.00 ~ 100.00 ℃ Humidity : -100.0 ~ 100.0 % RH Dry/wet bulb sensor
compensationCompensate the difference between the wet and dry bulb sensor after
removing the wit bulb sensor gauze.Scaling DC Voltage (V DC) : Input scaling depending on the range variation. Input filter 1 ~ 180 sec Input break
detectionUP scale (in case of the RTD input),
Operation stops when exceeding ±5 % of the range limit.Control mode Operation method selection Constant value control / program control selectable. Control action Pattern 100 patterns (100 segments / 1 pattern) Segment 2,000 segments max. PID group 16 group (temperature 4 zones X humidity 4 zones) Auto tuning Auto tuning depending on the target set value. Proportional band 0.00 ~ 600.00 ℃ (ON / OFF control when value is 0.00) Integral time 0.00 ~ 6,000 sec (OFF state when time is set to 0) Derivative time 0.00 ~ 6,000 sec (OFF state when time is set to 0) ON/OFF control Set the proportional band to 0.0 Direct/reverse control Depends on the direct/reverse action of control output. Hysteresis 0.1 ~ 600 ℃ (with humidity, wet bulb temperature or replaced value) Retransmission Output Temperatureㆍhumidity 4 - 20 ㎃ DC select among the present value(PV), set value(SV),
and output amount (MV)Scaling Automatically scales the high and low range (4 - 20 ㎃ DC). Alarm setting Set alarm System alarm : 4 contacts. Alarm 4 contacts per pattern Alarm type High/low alarm, low deviation alarm and etc (20 kinds) Absolute alarm Temperature : -100.00 ~ 500.00 ℃ Humidity : 0.0 ~ 100.0 % RH. Deviation alarm Temperature : -600.00 ~ 600.00 ℃ Humidity : -100.0 ~ 100.0 % RH. Hysteresis Temperature : 0.0 ~ 600.0 ℃ Humidity : 0.0 ~ 100 % RH. Power backup memory Saving device Internal flash and FRAM, Temperature / Humidity each 86,400 point. Saving function Save and restore the program information and set value and save the temperature humidity set value and indication value